top of page

Density monitoring system

Type: P580

 

Service intended

 

P580 series are designed to monitor the gas density of closed SF6 tank (for switchgear). It is capable of the measuring real time status of SF6 gas density. These series are equipped with the relay contact which has the three configurable independent units to sense and measure the instantaneous pressure rise.

 

Display

 

Analog indicator, operation and alarm status LED

 

Accuracy

 

±1.0 % at ambient temperature +20 °C (Indicator)
±2.5 % at ambient temperature -20 °C / +60 °C (Indicator)
±0.25 % at ambient temperature 0 °C ~ +50 °C (Current output)

 

Scale range

 

-0.1 ~ 0.1 MPa to -0.1 ~ 1.2 MPa

 

Working temperature

 

Ambient : -20 ~ 65 °C (Gas phase)
Storage : -50 ~ 60 °C maximum

 

System configuration

 

HART communication

 

Degree of protection

 

EN60529/IEC529/IP67

 

 

Standard features

Mechanical

 

Pressure connection

 

Stainless steel (316SS)

 

Element

 

Stainless steel (316SS) C-type bourdon tube

 

Case and cover

 

Stainless steel (304SS) Bayonet type

 

Window

 

Safety glass

 

Movement

 

Stainless steel (304SS)
Bimetal link (Temperature compensation)

 

Pointer

 

Black painted aluminium alloy

 

Process connection

 

G½"

 

Helium leak rate

 

Tested to confirm leakage rates of less than 10-8  mbar.L/sec

 

 

Standard features

Electrical

 

Input power and current consumption

 

12 ~ 36 V DC input, Max. 60 mA@DC 24 V

 

Display

 

Operating and alarm status LED

 

Parameter input

 

HART configurator

 

Output

 

Current output (4 ~ 20 mA, DC)
One instantaneous pressure rising alarm relay Three pressure limit alarm relay

 

Relay contact rate

 

Contact resistance : Max. 70MΩ
Contact rating : 2 A 30 VDC, 0.5 A 125 DC (Res.load)
Max switching voltage : 220 VDC / 250 VAC
Max switching power : 60 W / 62.5 VA

 

 

Download:  CATALOG 

Đồng hồ áp suất P580