Differential Ultra Low Pressure Transmitter with Local Indication
Type: DPU
Pressure 50…100kPa
Accuracy ±0.3~±1%FS
Output 4~20mA
Description
DPU model is ideal for the application (such as HVAC) with differential pressure, vacuum pressure, gauge pressure and especially low pressure of non-corrosive gases or air measured. Device for Ultra Low Pressure Transmitter, which is using MICOM, improved Accuracy and Temperature compensation. Analog output 4~20mA, 2wire and it provides LCD display.
Features
- CE Certified
- 4 digit Bar Graph LCD display
- Pressure Unit selection(Pa, mmH2O, mbar)
- % Display Mode
- Auto Zero
- 2Wire 4~20mA analog output
- Measuring range 0~50..100kPa diff.
- 0.3..1%FS accuracy
- Piezoresistive silicon cell
- Use with non-corrosive, non-ionic media
Applications
- Airflow Measurement
- Room Static Pressure
- VAV Box
- Lab/Fume Hood Control
- Clean Room Control
Specifications
Range
Range | 0~50, 100Pa ±50, ±100Pa | 0~200, 300Pa ±200, ±300Pa | 0~500 ... 100kPa ±500 ... ±100kPa |
Performance
Accuracy Thermal Effect(Zero) Thermal Effect(Span) | ±1%FS±1digit ±0.1%FS/℃ ±0.1%FS/℃ | ±0.5%FS±1digit ±0.05%FS/℃ ±0.05%FS/℃ | ±0.3%FS±1digit ±0.03%FS/℃ ±0.03%FS/℃ |
Compensated Temp. Range Operating Temp. Range | 0~50℃ -10~70℃ |
Electrical
Display Excitation Output Electrical Connection | 4 Digit Bar Graph LCD 11~28VDC 4~20mA (2Wire) Terminal Block |
---|
Physical
Proof Pressure Burst Pressure Vibration Shock Pressure Port Media-Wetted Materials Weight | 300%FS Max. 500%FS Min. 49.1m/s2{5G}, 10~500Hz 490m/s2{50G} 1/8″, 3/16″ Nipple BsP, SiO2, Si Rubber Approx. 250g |
---|
Download: CATALOG