General type temperature transmitter
Model: T990
Service intendedThese transmitters are recommended be used in the situation where the application of RTD signals to carry to a long distance or to guard against the heavy electrical field noise. The transmitters convert RTD inputs to an analog signal for a direct interface with indicators, recorders, controllers, PLC, DCS systems, and these can be used for a wide range of applications in process control, automatic machinery and hydraulic or pneumatic system design.
Advantages- Two wire 4 - 20 mA current output signal- RTD input- Measuring range from -50 ~ 400℃- Fixed range- Excellent accuracy and long term stability- Low - cost- Miniature design
Specification
Electrical specification
Excitation voltage : 12 ~ 36 VLoad resistance : Max. 500Ω at 24 VInfluence of excitation : 0.01% FSO/VBurnout : Upscale (Approx. 23 mA DC) orDown scale (Approx. 4 mA DC)Reverse polarity : ProtectedShock resistance : No change in performance after10Gs for 11msVibration : 5g (10 ~ 2,000 Hz)Response time (10 ~ 90%) : ±0.5 secondsAdjustment range : ±15% FSO/zero and span
Performance specificationAccuracy : ±0.2% FSONon - linearity : Better than 0.01% FSORepeatability : Better than 0.05% FSOLong term stability : Better than 0.05% FSO per monthAmbient temperature limits : -20 ~ 70℃Ambient humidity limits : 5 ~ 95% R.H
InputMeasuring element : Pt 100Ω at 0℃
OutputCurrent outputElectrical connection type : 2-wire techniqueFull scale output signal : 20 mA ±0.2%Zero measured output : 4 mA ±0.03%Other output signals available on request
Download: CATALOG